Polacel XE cooling towers

The Polacel cross flow cooling tower is quiet and economical, and has a high cooling capacity. The modular system can be easily adjusted to suit cooling requirements and the space available.
The cooling towers have optimal performance and run problem-free. The considerable savings in water usage (95%+), and the exceptionally low noise level make the economical crossflow cooling towers the best choice for both man and the environment.
Type | Wet surface (m2) | Q min (m3/h) | Q max (m3/h) | Dimensions | Weight | Number of engines | |||
---|---|---|---|---|---|---|---|---|---|
L (mm) | B (mm) | H (mm) | empty (kg) | operational (kg) | |||||
1,44 | 12 | 80 | 2.270 | 1.540 | 2.215 | 450 | 1.250 | 1 | |
2,88 | 23 | 160 | 2.710 | 2.270 | 2.215 | 880 | 2.450 | 2 | |
4,32 | 35 | 240 | 3.970 | 2.270 | 2.215 | 1.300 | 3.700 | 3 | |
5,76 | 46 | 320 | 5.230 | 2.270 | 2.215 | 1.740 | 4.900 | 4 | |
7,2 | 58 | 400 | 6.490 | 2.270 | 2.215 | 2.200 | 6.100 | 5 |
- All data is for information only. Please contact Polacel for certified data.
- All types are available with different air speeds.
- Polacel has extensive specifications for all cooling towers listed above.
XE cooling tower |
---|
![]() |
Polacel XT cooling towers
The Polacel cross flow cooling tower is quiet and economical, and has a high cooling capacity. The modular system can be easily adjusted to suit cooling requirements and the space available.
The cooling towers have optimal performance and run problem-free. The considerable savings in water usage (95%+), and the exceptionally low noise level make the economical crossflow cooling towers the best choice for both man and the environment.
Type | Wet surface (m2) | Q min (m3/h) | Q max (m3/h) | Dimensions | Weight | Number of engines | |||
---|---|---|---|---|---|---|---|---|---|
L (mm) | B (mm) | H (mm) | empty (kg) | operational (kg) | |||||
2,88 | 23 | 160 | 2.710 | 3.480 | 2.460 | 1.250 | 5.250 | 1 | |
2,88 | 23 | 160 | 2.710 | 3.480 | 2.960 | 1.415 | 5.520 | 1 | |
2,88 | 23 | 160 | 2.710 | 3.480 | 3.460 | 1.575 | 5.825 | 1 | |
5,76 | 46 | 320 | 5.320 | 3.480 | 2.460 | 2.425 | 10.425 | 2 | |
5,76 | 46 | 320 | 5.320 | 3.480 | 2.960 | 2.750 | 11.050 | 2 | |
5,76 | 46 | 320 | 5.320 | 3.480 | 3.460 | 3.050 | 11.550 | 2 | |
8,64 | 69 | 480 | 7.750 | 3.480 | 2.460 | 3.675 | 15.675 | 3 | |
8,64 | 69 | 480 | 7.750 | 3.480 | 2.960 | 4.200 | 16.575 | 3 | |
8,64 | 69 | 480 | 7.750 | 3.480 | 3.460 | 4.625 | 17.400 | 3 |
- All data is for information only. Please contact Polacel for certified data.
- All types are available with different air speeds.
- Polacel has extensive specifications for all cooling towers listed above.
XT cooling tower |
---|
![]() |
XT cooling tower |
---|
![]() |
|
Polacel XM cooling towers
The Polacel cross flow cooling tower is quiet and economical, and has a high cooling capacity. The modular system can be easily adjusted to suit cooling requirements and the space available.
The cooling towers have optimal performance and run problem-free. The considerable savings in water usage (95%+), and the exceptionally low noise level make the economical crossflow cooling towers the best choice for both man and the environment.
Type | Wet surface (m2) | Q min (m3/h) | Q max (m3/h) | Dimensions | Weight | Number of engines | |||
---|---|---|---|---|---|---|---|---|---|
L (mm) | B (mm) | H (mm) | empty (kg) | operational (kg) | |||||
17,3 | 138 | 952 | 7.620 | 10.060 | 8.656 | 13.500 | 38.280 | 1 | |
25,9 | 207 | 1.425 | 7.620 | 10.060 | 8.650 | 19.500 | 39.000 | 1 |
- All data is for information only. Please contact Polacel for certified data.
- All types are available with different air speeds.
- Polacel has extensive specifications for all cooling towers listed above.
XM cooling tower |
---|
![]() |
XM cooling tower |
---|
![]() |
|